ZN85-30kV(40.5kV) Indoor Handcart Vacuum Circuit Breaker
The ZN85 Indoor Handcart Vacuum Circuit Breaker (hereinafter referred to as the circuit breaker) is suitable for three-phase AC systems at 50Hz with a rated voltage of 35kV(40.5kV). It is designed for use in industrial enterprises, power plants, and substations for switching on and off load currents, overload currents, and fault currents. The circuit breaker features an upper and lower arrangement of the operating mechanism, effectively reducing the overall depth of the circuit breaker. The three-phase arc-extinguishing chamber and associated live parts are isolated by three independent epoxy resin insulated tubes, forming a composite insulation structure. The circuit breaker meets the air gap and creepage distance requirements under normal operating conditions, significantly reducing its overall size. The main circuit's vacuum arc-extinguishing chamber and moving and stationary conductive connections are installed within the insulating tube, with an inter-phase distance of only 300mm.
Vertical Layout & Compact Footprint: The circuit breaker and operating mechanism adopt an upper and lower layout structure, which effectively reduces the depth of the breaker.
Composite Insulation Structure: The three interrupters and associated live parts are isolated by three independent epoxy resin insulation cylinders, fulfilling normal operating air and creepage distance requirements while effectively minimizing overall volume.
Fixed Electrical Connections: The main circuit vacuum interrupter and moving/static conductor links are installed inside the insulation cylinders, making the phase distance only 300mm. All main circuit electrical connections adopt fixed connections for extremely high reliability.
Dedicated Spring Operating Mechanism: Designed specifically for this vertical layout, the spring mechanism is installed inside the framework and acts as an integral, inseparable part of the breaker, featuring a simple design with output curves and performance tailored to 40.5kV requirements.
|
Tech. parameters |
Unit |
Data
|
|
|
Rated voltage
|
KV |
40.5 |
|
|
Rated current |
A |
1250 1600 2000 |
|
|
Rated frequency |
Hz |
50 |
|
|
Rated short circuit breaking current |
KA |
25 |
31.5 |
|
Rated short-circuit closing current (peak value) |
KA |
63 |
80 |
|
4s rated short-time withstand current |
KA |
25 |
31.5 |
|
Rated peak withstand current |
KA |
63 |
80 |
|
1min power frequency withstand voltage |
KV |
95 |
|
|
Tech. parameters |
Unit |
data |
|
Lightning impulse withstand voltage (peak value) |
KV |
185 |
|
Rated operating sequence |
|
0-0.3s-CO-180s-CO |
|
Rated short circuit breaking current breaking times |
Second-rate |
20 |
|
Mechanical life |
Second-rate |
10000 |
|
Breaking time |
ms |
≤80 |
|
Breaking current of single capacitor |
A |
630 |
|
Back-to-back capacitor bank breaking current |
A |
400 |
|
Rated operating voltage |
V |
-110/~110,-220/-220 |
Operating Environment Conditions:
Based on the technical requirements of the ZN85-40.5 series and standard indoor high-voltage switchgear parameters, it is designed for standard indoor environments free from flammable substances, explosive hazards, chemical corrosion, and severe vibrations.
(Note: If specific site parameters like temperature, humidity, or altitude require customization, they can be coordinated with our engineering team.)
Frequently Asked Questions (FAQ):
Q1: What power systems are compatible with the ZN85-40.5 circuit breaker?
A: It is designed for three-phase AC 50Hz power systems with a rated voltage of 40.5kV.
Q2: What is the main structural design of the ZN85-40.5?
A: It features an upper and lower layout structure for the breaker and mechanism, utilizing three independent epoxy resin insulation cylinders to form a compact composite insulation structure with a 300mm phase distance.
Q3: What type of operating mechanism does this circuit breaker use?
A: It uses a custom-designed spring operating mechanism built directly into the breaker framework, featuring output characteristics precisely tailored to 40.5kV requirements.
Q4: Is the mechanism difficult to maintain?
A: No. The operating mechanism is designed to be maintenance-free, offering high operational flexibility, long service life, and easy overall upkeep.
CKG4 High Voltage Vacuum Contactor 12kV
CKG4 high-voltage vacuum contactors, the AC vacuum ...
See More
CKG4B 7.2kV 12kV 1250A High Voltage Vacuum Contactor
This series of high-voltage vacuum contactors, the AC ...
See More
VS1(ZN63A)-12kV High Voltage Indoor Vacuum Circuit Breaker (Fixed Type)
VS1(ZN63A)-10kV(12kV) Indoor high-voltage Vacuum Circuit ...
See More
Vacuum Contactor (JCZ8C-24kV )
This series of medium-voltage vacuum contactors is suitable ...
See More
VS1(ZN63A)-10kV(12kV) Side-Mounted Indoor Vacuum Circuit Breaker
VS1(ZN63A)-10kV(12kV) Side-Mounted Indoor Medium-voltage ...
See More
CKJ40 2kV Series Low Voltage Vacuum Contactor
This series of vacuum contactors reaches a high level of ...
See More
CKJ20-160/250/400 Low Voltage Vacuum Contactor Switch
This CKJ20 series of vacuum contactor switch is suitable ...
See More
Low Voltage Vacuum Contactor (CKJ20-630/1250A)
This series of vacuum contactors is suitable for ...
See MoreProduct Search
Here you can choose products online and find the products you want more quickly and accurately.
Customized Consultation
If you want to customize a product, please contact us, and our team is more than happy to assist you.
Product Procurement
If you want to purchase a product, please contact us and we will provide you with product information and a quotation.
Chennuo Electric Technology Group Co., Ltd
Tel:+86 19303791130
Email:sales@chennuojt.com
Add:No. 9 Duyu Street, Luolong District, Luoyang City, Henan Province, China