ZW32-12 Capacitor-Powered Insulation Column Circuit Breaker
Fully integrated circuit breaker body, feeder terminal FTU, power PT, and connection cable, and the deep integration of primary and secondary equipment is in place in one step, which solves the problems of remote signal jitter and terminal line loss collection in the distribution network; It realizes the functional requirements of distribution network segmented line loss management, in-situ feeder automation, single-phase grounding fault detection, factory pre-installation, plug and play, etc. Functional features: It has adaptive in-situ feeder automation, and realizes in-situ line selection, section positioning and isolation of single-phase grounding faults through control logic such as short-circuit or grounding fault detection technology, pressure-free switching, and adaptive delay call closing of fault paths; Cooperate with the secondary closing of the substation to realize the automatic isolation of permanent faults in situ and the restoration of power supply in the upstream area of the fault. Overall requirements: The new electronic sensor is deeply integrated with the column circuit breaker, improves the reliability of equipment operation, facilitates on-site operation and maintenance, meets the functional requirements of local feeder automation, and realizes equipment interconnection, state awareness, resource utilization, and intelligent decision-making functions.
Safe and reliable: light weight (85kg) to avoid the risk of accidents after installation, reduce the primary auxiliary equipment, reduce the risk of equipment failure, and eliminate the potential safety hazards of remote control caused by automation.
Operation function: realize the selective tripping of the short-circuit fault of the overhead line of the distribution network (multi-level precise differential coordination), realize the selective automatic isolation of the single-phase grounding fault of the overhead line of the distribution network (differential coordination), and solve the line loss assessment problem of the overhead line of the distribution network.
Product innovation: the use of high-precision, wide-range electronic sensor to replace the traditional electromagnetic transformer, to achieve measurement/protection/monitoring three-in-one compatibility, sensor and body pole integral sealing process, to achieve deep integration, power mode to solve the power supply PT, modular, standardized design, support hot swap, easy installation.
High degree of intelligence: the equipment does not depend on the master station, and when the line fails, it can accurately and quickly isolate the smallest fault area of the short circuit or single-phase grounding fault; the terminal can independently judge the short-circuit or single-phase grounding fault by itself and issue isolation instructions.
The name of the parameter | Unit | Parameter value |
Rated voltage | KV | 10 |
Rated cable charging breaking current | A | 25 |
Current rating | A | 630/1250 |
Rated short-circuit interrupting current | KA | 20/25 |
Rated peak withstand current (peak) | KA | 50/63 |
The frontal point is resistant to current for a short time | KA | 20/25 |
Rated short-circuit closing current (peak) | KA | 50/63 |
Mechanical life | times | 20000 |
Rated number of short-circuit breaking current interruptions | times | 30 |
Power frequency withstand voltage (1min) :(wet) (dry) interphase, ground/fracture | KV | 42/48 |
Withstand voltage (peak) of lightning impulse interphase, to ground/fracture | KV | 75/85 |
Voltage sensors |
||
The name of the parameter | numeric value | |
Rated conversion ratio | Phase: 600A/1V, Zero Sequence: 20A/0.2V | |
Accuracy (including 15m cable) | Phase: protection 5P10 level, metering 0.5S level 3-in-1 compatible Zero sequence: <1% (1%-120%ln, protection 10P10 level | |
How it works | Low power consumption electromagnetic type | |
Temperature range | -40℃-70℃ | |
Load impedance | Not less than 20kΩ |
Current sensors
The name of the parameter | numeric value |
Rated conversion ratio | Phase voltage: (10kV/ √3)/(3.25V/ √3), zero sequence (10kV/ √3)/(6.5V/ √3) |
Accuracy (including 15m cable) | Phase voltage: 0.5/3P level, zero sequence voltage: 3P |
How it works | Capacitor voltage divider |
Temperature range | -40℃-70℃ |
Load impedance | 10pC,14.4kV |
Insulation resistance when combined with a switch (switch opposite) | ≥25MΩ |
Load impedance | The input impedance of the terminal > 10MΩ, and the input impedance of the distribution line loss acquisition module > 10MΩ |
Current sensors
The name of the parameter | numeric value |
Rated conversion ratio | Phase voltage: (10kV/ √3)/(3.25V/ √3), zero sequence (10kV/ √3)/(6.5V/ √3) |
Accuracy (including 15m cable) | Phase voltage: 0.5/3P level, zero sequence voltage: 3P |
How it works | Capacitor voltage divider |
Temperature range | -40℃-70℃ |
Load impedance | 10pC,14.4kV |
Insulation resistance when combined with a switch (switch opposite) | ≥25MΩ |
Load impedance | The input impedance of the terminal > 10MΩ, and the input impedance of the distribution line loss acquisition module > 10MΩ |
LW36-40.5 series outdoor sulfur hexafluoride circuit breaker (SF6)
LW36-40.5/1250A-2000A high-voltage outdoor sulfur ...
See MoreZW32 Outdoor Vacuum Circuit Breaker
The device is an intelligent complete set of equipment ...
See MoreZW32-12 Pole-Mounted Outdoor Vacuum Circuit Breaker
The primary and secondary fusion of a complete set of ...
See MoreZW32-12 Outdoor Vacuum Circuit Breaker
The primary and secondary fusion complete sets of column ...
See MoreZW32-12 Outdoor Pole-Mounted Vacuum Circuit Breaker
The primary and secondary fusion complete sets of column ...
See MoreZW7-40.5 Outdoor High Voltage Vacuum Circuit Breaker
This series of outdoor high-voltage vacuum circuit breakers ...
See MoreZW7A-40.5 Outdoor High Voltage Vacuum Circuit Breaker
This series of outdoor high-voltage vacuum circuit breakers ...
See MoreZW7B-40.5 Outdoor Vacuum Circuit Breaker
This series of outdoor high-voltage vacuum circuit breakers ...
See MoreProduct Search
Here you can choose products online and find the products you want more quickly and accurately.
Customized Consultation
If you want to customize a product, please contact us, and our team is more than happy to assist you.
Product Procurement
If you want to purchase a product, please contact us and we will provide you with product information and a quotation.
Tel:+86 15538537280
Email:lycnelectric@163.com
Add:No. 9 Duyu Street, Luolong District, Luoyang City, Henan Province