JCZ1-24kV Vacuum Contactor
This series of high-voltage vacuum contactors are made of high-quality vacuum switch tubes, with metal frames and insulating brackets, with excellent breaking performance, suitable for single-phase or two-phase power network systems below 24KV, for long-distance connection and breaking, frequent start and control of resistive, inductive and capacitive loads and other occasions. JCZ1 series unipolar high-voltage vacuum contactor is often used in power protection occasions such as signal source arc suppression, detuning neutral point grounding, load box, etc., and is used as a grounding main switch, which has the advantages of small size, fast closing and opening speed, strong breaking capacity, etc., and can be used in 24kv power system or 12kv power system at an altitude of more than 4000 meters.
Choose high-quality vacuum switch tubes, with metal frames and insulating brackets.
It has excellent breaking performance.
It has the advantages of small size, fast closing and opening speed, and strong breaking capacity.
The name of the parameter | Model | 160、250/24 | 400/24 | 530/24 | 800/24 | 1000、1250/24 |
Rated voltage of the main circuit | (KV) | 24 | 24 | 24 | 24 | 24 |
Rated current of the main circuit | (A) | 160、250 | 400 | 630 | 800 | 1000、1250 |
The ability to close the main path | (A/100times) | 2500 | 4000 | 6300 | 6000 | 8000 |
The main circuit is on/off | (A/25times) | 2000 | 3200 | 5000 | 6000 | 8000 |
Suction limit breaking capacity | (A/3times) | 4000 | 4500 | 6300 | 3000 | 10000 |
Mechanical life | (10,000times) | 100 | 100 | 100 | 100 | 100 |
Aircraft war cargo hit the clouds | (10,000times) | 10 | 10 | 10 | 10 | 10 |
Electrical life AC3 | (10,000times) | 25 | 25 | 25 | 25 | 25 |
Permanent magnet mechanism life | (10,000times) | 10 | 10 | 10 | 10 | 10 |
Power frequency withstand voltage of main circuit (fracture) | (KV) | 65 | 65 | 65 | 65 | 65 |
Phase-phase/phase-to-ground power frequency withstand voltage | (KV) | 65 | 65 | 65 | 65 | 65 |
Withstand lightning impulse voltage | (KV) | 125 | 125 | 125 | 125 | 125 |
Rated operating frequency | (times/h) | 150 | 150 | 150 | 150 | 150 |
The operating frequency of the permanent magnet mechanism | (times/h) | 30 | 30 | 30 | 30 | 30 |
Terminal pressure | (N) | >100 | >100 | >100 | >100 | >100 |
Contact opening distance | (mm) | 10±1 | 10±1 | 10±1 | 10±1 | 10±1 |
Overtravel | (mm) | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 |
Main loop resistance | (μΩ) | ≤200 | ≤200 | ≤200 | ≤200 | ≤200 |
CKG4-12 High Voltage Vacuum Contactor
This series of high-voltage vacuum contactors, the AC ...
See MoreHigh Voltage Vacuum Contactor CKG4(B)
This series of high-voltage vacuum contactors, the AC ...
See MoreVacuum Circuit Breaker with Permanent Magnetic Actuator (ZN3A-12 )
This series of high-voltage permanent magnet vacuum ...
See MoreHigh Voltage Vacuum Load Switch (FZNS16)
This series of permanent magnet vacuum load switch selects ...
See MoreVacuum Contactor (JCZ8C-24kV )
This series of high-voltage vacuum contactors is suitable ...
See MoreHigh Voltage Vacuum Contactor (JCZ9-40.5kV)
This series of 40.5KV high-pressure vacuum contactor is a ...
See MoreJCZ1-40.5kV Series Vacuum Contactor
This series of high-voltage vacuum contactors are made of ...
See MoreFZ(R)N35-40.5(D) series indoor high-voltage vacuum load switch-fuse combination electrical appliances
Indoor high-voltage AC vacuum load switch-fuse combined ...
See MoreProduct Search
Here you can choose products online and find the products you want more quickly and accurately.
Customized Consultation
If you want to customize a product, please contact us, and our team is more than happy to assist you.
Product Procurement
If you want to purchase a product, please contact us and we will provide you with product information and a quotation.
Tel:+86 15538537280
Email:lycnelectric@163.com
Add:No. 9 Duyu Street, Luolong District, Luoyang City, Henan Province