VCNR-12 Handcart Vacuum Contactor with Fuse
This series of products is suitable for three-phase AC indoor high-voltage switchgear with AC 50-60Hz and main circuit rated operating voltages of 7.2kV and 12kV. Its function combination is flexible, its structure is compact and reliable, and it has multiple protection functions. It has a long service life and can be operated frequently. It can be widely used for breaking and closing AC motors, transformers and other load circuits, and can also be used for capacitor reactive power compensation. The contactor can be selected as fixed type or handcart type. The handcart type can be used with 550, 650 and 800mm wide KYN28A (GZS1) type center cabinets, and can be used to replace VSC/P contactors. The main circuit of the contactor adopts a solid-sealed pole structure with good insulation performance and long life. The mechanism has electromagnetic holding and permanent magnet structures. It is stable and reliable and can operate frequently. With the fuse quick-blow protection, it forms a perfect F-C combination electrical appliance.
This series of products is suitable for three-phase AC indoor high-voltage switchgear with AC 50-60Hz and main circuit rated operating voltages of 7.2kV and 12kV.
The main circuit adopts a solid-sealed pole structure with good insulation performance and long life. The mechanism has electromagnetic holding and permanent magnet structures, which is stable and reliable and can operate frequently.
Combined with fuse quick-blow protection, it forms a perfect F-C combination appliance.
Project |
Unit |
Parameter |
||
Rated voltage |
KV |
7.2 |
12 |
|
Rated frequency |
HZ |
50 |
||
Rated operating current |
A |
315 |
60 |
|
Rated peak withstand current |
KA |
10 |
||
Rated short circuit breaking current |
KA |
50 |
||
Expected short circuit making current |
KA |
130 |
||
Rated short-time withstand current |
A-s |
767102 |
||
Usage categories |
AC-3 AC-4 |
|||
Insulation level |
1min work quota withstand pressure |
KV |
32 |
42 |
Lightning impulse withstand voltage |
KV |
60 |
75 |
|
Mechanical life |
Permanent magnet (mechanical retention) |
Thousands of times |
20 |
|
electrical hold |
Thousands of times |
25 |
||
Rated working day |
long-term working system |
|||
Rated operating frequency |
10,000/h |
300 |
||
Main circuit resistance |
μ |
≤300(Does not include fuse) |
||
Auxiliary and control circuit rated voltage |
V |
AC/DC110/220 |
Project |
Unit |
Parameter |
|
Rated voltage |
KV |
7.2 |
12 |
Rated current |
A |
~315 |
~360 |
Anticipated short circuit breaking current |
KA |
40、50 |
|
Impactor form |
Spring striker |
||
Impactor energy |
J |
>1 |
VCN3-12 Series Handcart Vacuum Contactor
This series of vacuum contactors is a new type of ...
See MoreHorizontal High Voltage Vacuum Contactor
This series of horizontal high-voltage vacuum contactor is ...
See MoreBypass Switch (High Performance Switch)
CNF series vacuum switch is used for bypass protection of ...
See MoreProduct Search
Here you can choose products online and find the products you want more quickly and accurately.
Customized Consultation
If you want to customize a product, please contact us, and our team is more than happy to assist you.
Product Procurement
If you want to purchase a product, please contact us and we will provide you with product information and a quotation.
Tel:+86 15538537280
Email:lycnelectric@163.com
Add:No. 9 Duyu Street, Luolong District, Luoyang City, Henan Province